Obsolete

This product is now obsolete

XP95 I.S. Manual Call Point – MEDC Style (Break Glass)

55000-960APO

The Manual Call Point is used to manually initiate an alarm signal on the fire detection system. The Manual Call Point is suitable for use in areas where explosive atmospheres are, or may be, present.

  • Suitable for intrinsically safe and weatherproof applications
  • Suitable for use on Zones 2, 1 & 0
  • EN 54-11 Certified
  • Reports an alarm in under 0.2 seconds
  • Made of glass-reinforced polyester
  • XP95 & Discovery compatible
Technical specification
General
Warranty

3 year

Mechanical
Colour

Red

Weight

240g

Product length

126mm

Product width

120mm

Product depth

67mm

Detection principle

Operation of a switch.

Key type

DIN Manal Call Point reset key

Product length

4.96in

Product width

4.72in

Product depth

2.64in

Conformance
Approvals

BASEEFA

Electrical
Protocol voltage (max)

9V

Protocol voltage (min)

5V

Protocol voltage

5 to 9V peak to peak

Quiescent current

300μA

Quiescent current tested at

24V dc

Environmental
IP rating Value

IP66

Downloads
Approvals
Compatible panels

Compatible panels

We partner with panel manufacturers around the globe.

Training and Support

Training and Support

Designed especially for you by our in-house expert team.