Apollo Fire Detectors | XP95 AV Control Module - Isolating

XP95 AV Control Module – Isolating

55000-852APO

The XP95 AV Control Module is used to control and monitor the operation of a circuit of conventional sounders or bells.

  • EN 54-17 & EN 54-18 Certified
  • Allows sounders to be operated 1 second on, 1 second off
  • May be synchronised with loop sounders
  • Suitable for semi flush or surface mounting
  • XP95, Discovery compatible
Technical specification
General
Warranty
10 year
Mechanical
Colour
White
Weight
240g
Product length
48mm
Product width
150mm
Product depth
90mm
Product length
1.89in
Product width
5.91in
Product depth
3.54in
Conformance
Standards
EN 54-17 EN 54-18
Approvals
FG LPCB VdS CPR
Electrical
Protocol voltage (min)
5V
Protocol voltage (max)
9V
Protocol voltage
5 to 9V peak to peak
Supply voltage (max)
28V dc
Supply voltage (min)
17V dc
Supply voltage (Vmin-Vmax)
17 to 28V dc
Power-up surge current
2.6mA
Maximum power-up time
<1 second
On resistance
0.2Ω
Sounder circuit voltage (max)
32V dc
Sounder circuit currents
30V dc
Sounder circuit currents tested at
1A
Environmental
Humidity
0% to 95% (no condensation or icing)
Humidity Note
no condensation or icing
Humidity (max)
95% RH
Humidity (min)
0% RH
Operating temperature
-20 to 70°C
Operating temperature (max)
70°C
Operating temperature (min)
-20°C
IP rating
Designed to
IP rating Value
IP54
Operating temperature
-4 to 158°F
Operating temperature (max)
158°F
Operating temperature (min)
-4°F
Downloads
Approvals
Compatible panels

Compatible panels

We partner with panel manufacturers around the globe.

Training and Support

Training and Support

Designed especially for you by our in-house expert team.