Obsolete

This product is now obsolete

XP95 I.S. Ionisation Smoke Detector

55000-540APO

Full details of the principles of operation and electrical description are published in the XP95 Engineering Product Guide. Information on the performance of XP95 in adverse environmental conditions is also given in this guide. XP95 IS detectors have the same operating characteristics as the standard versions.

Technical specification
General
Warranty

10 year

Applications

Car parks/loading bays

Hazardous areas

Medium to large buildings

Offshore platforms

Refineries

Warehouses

Fire Type

Fast burning, flaming fires

Mechanical
Colour

White

Sensor configuration

Twin compensating chambers using one single sided ionising radiation source.

Conformance
Approvals

BV

BASEEFA

BOSEC

LPCB

PESO (CCoE)

IECEx

CPR

MED

Performance
Chamber type

Chevron

Electrical
Protocol voltage

5 to 9V peak to peak

Protocol voltage (max)

9V

Protocol voltage (min)

5V

Quiescent current

300μA

Polarity

L1 & L2 are polarity sensitive

Environmental
Humidity Note

no condensation or icing

Downloads