Technical specification
General
Warranty

10 year

Applications

Bedrooms

Cafes

Escape routes

Hotels

Restaurants

Retail

B&Bs/guest houses

Offices

University campuses

Fire Type

Slow burning, smouldering fires

Mechanical
Colour

Black

Finish

Gloss

Sensor configuration

Chamber with surface-mount infrared emmiter and prism. Solid state integrated photo-diode and amplifier.

Weight

146g

Materials housing

Polycarbonate

Materials terminals

Tin plated stainless steel

Product diameter

100mm

Detection principle

Photo-electric light scattering.

Product diameter

3.94in

Conformance
Standards

EN 54-7

EN 54-17

Approvals

LPCB

CPR

Performance
Analogue value nominal

23

Analogue value (- tolerance)
0
Analogue value (+ tolerance)

4

Analogue value

23 +4/-0

Alarm level analogue value

55

Chamber type

PureLight

Electrical
Protocol voltage

5 to 13V peak to peak

Protocol voltage (max)

13V

Protocol voltage (min)

5V

Power-up surge current

0.56mA

Status indicator – Alarm

Red

Status indicator – Fault

Flashing yellow

Quiescent current

350μA

Quiescent current tested at

24V dc

Terminal functions L2

+L2 Loop in & out positive

Terminal functions L1 in

-L1 in Loop (isolated) negative

Terminal functions L2 out

-L1 out Loop (isolated) negative

Terminal functions +R

+R Remote indicator positive connection

Terminal functions -R

-R Remote indicator negative connection

Polarity

L1 & L2 are polarity sensitive

Status indicator – Isolate

Yellow

Status indicator – Poll

Green

Sampling frequency

Once per second

Environmental
Humidity (max)

95% RH

Humidity (min)

0% RH

Humidity Note

no condensation or icing

Humidity

0% to 95% (no condensation or icing)

Operating temperature

-40 to 70°C

Operating temperature (max)

70°C

Operating temperature (min)

-40°C

IP rating Value

IP44

Effect of wind speed

None

Wind speed test

Tested up to 10m/s

Operating temperature

-40 to 158°F

Operating temperature (max)

158°F

Operating temperature (min)

-40°F

Downloads
Approvals
Accessories

The Soteria Dimension Mounting Box is moulded from white flame-retardant polycarbonate. Positions for either side or top cable entry are marked on the outside of the Mounting Box to ensure correct cable positioning. An arrow has been placed on the rim to assist in correct orientation of the detector. Placing the Mounting Box in the correct orientation in the installation aperture, it is secured into position by screwing down the self-aligning fixing tabs.

Compatible panels

Compatible panels

We partner with panel manufacturers around the globe.

Training and Support

Training and Support

Designed especially for you by our in-house expert team.