Apollo Fire Detectors | Discovery Marine Optical Smoke Detector [SIL2]

Discovery Marine Optical Smoke Detector [SIL2]

58000-600MAR

The Discovery Marine Optical Smoke Detector are high-specification devices using the light scatter principle to quickly detect fire while effectively managing false alarms.

  • Reliable fire detection in areas with a very wide temperature range from -40°C to +70°C
  • Five operating modes suitable for a range of applications where unique response behaviour is required
  • Drift compensation to ensure constant sensitivity
  • Ideal for accommodation decks, passages and escape routes
  • 58000-600MAR is certified to a broad range of marine approvals and is EAC approved
  • 58000-600MAR has been assessed and certified for use in a safety function, to SIL level 2
Technical specification
General
Warranty

10 year

Applications

Bedrooms

Escape routes

Large vessels

Marine

Fire Type

Slow burning, smouldering fires

Mechanical
Colour

White

Sensor configuration

Horizontal optical bench housing infra-red emitter and sensor, arranged radially to detect forward scattered light.

Weight

105g

Materials housing

Polycarbonate

Materials terminals

Nickel plated stainless steel

Product length

42mm

Product diameter

100mm

Detection principle

Photo-electric light scattering.

Product length

1.65in

Product diameter

3.94in

Conformance
Standards

EN 54-7

Approvals

BV

DNV.GL

CCS

LR

ESC

MED

Performance
Analogue value nominal

23

Analogue value (- tolerance)
0
Analogue value (+ tolerance)

4

Analogue value

23 +4/-0

Alarm level analogue value

55

Chamber type

Chevron

Electrical
Protocol voltage

5 to 9V peak to peak

Protocol voltage (max)

9V

Protocol voltage (min)

5V

Power-up surge current

1mA

Maximum power-up time

10 seconds

Status indicator – Alarm

Red

Quiescent current

300μA

Quiescent current tested at

24V dc

Supply voltage (max)

9V dc

Supply voltage (min)

5V dc

Supply voltage (Vmin-Vmax)

5 to 9V dc

Terminal functions +R

+R Remote indicator positive connection

Terminal functions -R

-R Remote indicator negative connection

Polarity

L1 & L2 are polarity insensitive

Sampling frequency

Once per second

Environmental
Humidity (max)

95% RH

Humidity (min)

0% RH

Humidity Note

no condensation or icing

Humidity

0% to 95% (no condensation or icing)

Operating temperature

-40 to 70°C

Operating temperature (max)

70°C

Operating temperature (min)

-40°C

IP rating

Designed to

Operating temperature

-40 to 158°F

Operating temperature (max)

158°F

Operating temperature (min)

-40°F

Downloads
Approvals
Compatible panels

Compatible panels

We partner with panel manufacturers around the globe.

Training and Support

Training and Support

Designed especially for you by our in-house expert team.