The VSO base sounder is designed to work with a variety of detector brands to provide a cost-effective sounder solution.
As standard the VSO comes with 32 sounder toneswith a two-stage alarm override which is activated by a third negative wire from the panel.
Suitable for conventional and two wire (SAV-WIRE) fire alarm systems. Cover plate sold separately.
Part No.
507-001
Audible Signal
Siren
Visual Signal
None
Voltage
18-30
Mounting
Ceiling
Ingress Protection
IP21C
Temp. Range (°C)
-20 to +70
Colour (Body)
Apollo White
Material
ABS
Weight (kg)
0.11
Part No.
507-020
Audible Signal
Siren
Visual Signal
None
Voltage
18-30
Mounting
Ceiling
Ingress Protection
IP21C
Temp. Range (°C)
-20 to +70
Colour (Body)
Hochiki Cream
Material
ABS
Weight (kg)
0.11
| Part No. | Audible Signal | Visual Signal | Voltage | Mounting | Ingress Protection | Temp. Range (°C) | Colour (Body) | Material | Weight (kg) |
|---|---|---|---|---|---|---|---|---|---|
| 507-001 | Siren | None | 18-30 | Ceiling | IP21C | -20 to +70 | Apollo White | ABS | 0.11 |
| 507-020 | Siren | None | 18-30 | Ceiling | IP21C | -20 to +70 | Hochiki Cream | ABS | 0.11 |
Sound Output, Typical (dBA) - High
93.8
Sound Output, Typical (dBA) - Med
90.4
Sound Output, Typical (dBA) - Low
88.7
Max Current Consumption - High
12
Max Current Consumption - Med
8
Max Current Consumption - Low
6
No. of Tones
32
Operating Frequency (Hz)
440 – 2900
| Sound Output, Typical (dBA) | Max Current Consumption | No. of Tones | Operating Frequency (Hz) | ||||
|---|---|---|---|---|---|---|---|
| High | Med | Low | High | Med | Low | ||
| 93.8 | 90.4 | 88.7 | 12 | 8 | 6 | 32 | 440 – 2900 |
Cover Plate
507-006
White cover plate that can be used in place of a detector to create a standalone ceiling sounder.