Technical specification
Mechanical
Colour
White
Weight
83g
Materials housing
Polycarbonate
Product diameter
100mm
Product depth
36mm
Product depth
1.42in
Product diameter
3.94in
Conformance
Approvals
  • FM
  • UL
  • ULC
Electrical
Protocol voltage
5 to 9V peak to peak
Protocol voltage (max)
9V
Protocol voltage (min)
5V
Quiescent current
340μA
Environmental
Humidity (max)
95% RH
Humidity (min)
0% RH
Humidity Note
no condensation or icing
Humidity
0% to 95% (no condensation or icing)
Operating temperature
0 to 55°C
Operating temperature (max)
55°C
Operating temperature (min)
0°C
Operating temperature
32 to 131°F
Operating temperature (max)
131°F
Operating temperature (min)
32°F